Design with ac input /output 380vac 3 Phase only.
IGrid TT 10KW is a 3 Phase 10000w 48Vdc On & Off Grid Solar Power Inverter With Max MPPT 14850W Solar Inverter Pure Sine Wave Inverter ,it can feedback to Grid and make energy storage in to Battery bank. This 10KW hybrid Solar Inverter have 3 Operation Modes: Grid-tied, Off-Grid, On & Off Grid.
|
Product Main Features
- 10000W 48V Pure Sine Wave Inverer + 14850W MPPT Solar Charger + 40A Battery Charger
- Max PV Input 900Vdc
- Built-in 40A Battery Charger
- Works With 380~415Vac Load Only
- Works With 48v Battery System only
- Max Grid-Tie conversion efficiency up to 96%
- Peak inverter efficiency 93%
- High efficiency transformerless design
- Large LCD display of comprehensive system info
- RS232 and USB interface available
- User programmable functions
- Bundled Free monitoring software with setting programs
- CE, VDE4105 , AS 4777 certified
- Supports Parallel Function up to 6 units Max(internal Parallel kits )
MODEL |
IGrid TT 10KW |
Phase
|
3-phase in / 3-phase out
|
Maximum PV input power
|
14850 W
|
Rated output power
|
10000 W
|
Maximum charging power
|
9600 W
|
GRID-TIE OPERATION
|
|
PV INPUT(DC)
|
|
Nominal DC Voltage Maximum
|
720 VDC / 900 VDC
|
Start-up Voltage lnitial Feeding
|
320 VDC / 350 VDC
|
MPP Voltage Range
|
400 VDC ~ 800 VDC
|
Number of MPP Trackers
|
2 / 2 x 18.6 A
|
GRID OUTPUT(AC)
|
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Output Voltage Range
|
184-265 VAC* per phase
|
Nominal Output Current
|
14.5 A per phase
|
Power Factor
|
|
EFFICIENCY
|
|
Maximum Conversion
|
96%
|
European Efficiency@Vnominal
|
95%
|
OFF-GRID OPERATION
|
|
AC INPUT
|
|
AC Start-up Voltage Auto
|
120 – 140 VAC per phase / 180
|
Acceptable lnput Voltage Range
|
170 – 280 VAC per phase
|
Maximum AC lnput Current
|
40 A
|
PV INPUT(DC)
|
|
Maximum CD Voltage
|
900 VDC
|
MPP Voltage Range
|
400 VDC ~ 800 VDC
|
Number of MPP Trackers
|
2 / 2 x 18.6 A
|
BATTERY MODE OUTPUT(AC)
|
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Output Waveform
|
Pure Sine wave
|
Efffficiency (DC to AC)
|
91%
|
HYBRID OPERATION
|
|
PV INPUT (DC)
|
|
Nominal DC Voltage
|
720 VDC / 900 VDC
|
Start-up Voltage
|
320 VDC / 350 VDC
|
MPP Voltage Range
|
400 VDC ~ 800 VDC
|
Number of MPP Trackers
|
2 / 2 x 18.6 A
|
GRID OUTPUT (AC)
|
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Output Voltage Range
|
184-264.5 VAC* per phase
|
Nominal Output Current
|
14.5 A per phase
|
AC INPUT
|
|
AC Start-up Voltage Auto
|
120 – 140 VAC per phase / 180
|
Acceptable lnput Current
|
170 – 280 VAC per phase
|
Maximum AC lnput Current
|
40 A
|
BATTERY MODE OUTPUT (AC)
|
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
Efficiency (DC to AC)
|
91%
|
BATTERY & CHARGER
|
|
Nominal DC Voltage
|
48 VDC
|
Maximum Charging Current
|
Default 60A, 10A – 200A
|
GENERAL
|
|
PHYSICAL
|
|
Dimension,D X W X H (mm)
|
167.5 x 500 x 622
|
Net Weight (kgs)
|
45
|
INTERFACE
|
|
Communicaltion Port
|
RS-232/USB and CAN Interface
|
lntelligent Slot
|
Optional SNMP, Modbus and AS-400 cards available
|
ENVIRONMENT
|
|
Humidity
|
0 ~ 90% RH (No condensing)
|
Operating Temperature
|
-10 to 55°C
|
Altitude
|
0 ~ 1000 m**
|
Értékelések